| Location |
IPR Continuous Computing Center, Wilmington, DE United States |
About Company |
IPR International, LLC was founded on a simple concept: that technology will change at such a rapid pace that most mid-size organizations will not be able to keep up with it, and thus that we would dedicate ourselves to providing the best-of-breed, state-of the-art data protection technologies available so that our clients can focus on their core business operations with the secure knowledge that their electronic data is safe and accessible to them at all times.

|
| Facility |
Facility
- Tier III data center
- Data center built by JP Morgan Chase
- Built in 1988 (23 story office building) - 1,260 acre site
- LEED Certified Silver Space
- Continuous monolithic slab poured on reinforced concrete footings & fireproof steel frame
- 30,000 Sq. Ft. of raised floor with additional expansion capacity
- Floor Loading: 150lb. /sq. foot live load
- Walking distance to area Restaurants, Hotels and Amtrak Station
- Approximately 20 miles from Philadelphia International Airport
- 500-year flood plain
HVAC
- Two new fully redundant 150 ton modular chillers
- 2,000 Tons cooling redundancy
- Two pump redundancy - Building system is fall back system
- 27 BOHN DX type self-contained water service units
- 20-80 ton chilling capacity
- Condenser water system cools two building plate and frame heat exchangers
- Centrifugal fans blow through four cells at 583 tons each.
- Electric resistance heating from fan powered VAV boxes located at perimeter
- Data Canter Heat Exchangers
- 3000 GPM primary flow
- 3000 GPM secondary flow (total flow)
|
| Power |
- Two 2000 KVA transformer for redundancy and either of which is designed to power Data Center.
- Incoming Electric Services
- Two 13.8 KV incoming feeders from DELMARVA Power Company’s Brandywine sub-station. The unit feeds an automatic transfer controller. The ATS selects which feeder will power the two [2] 2000 KVA sub-station transformers.
- Sub-Stations:
- Number: 2 [3A-3B and 4A-4B]
- Capacity: 2000 KVA each side
- Voltage: 277/480 VAC
- Phase: 3 Phases
- Dual power availability to each rack unit from independent power distribution units (PDUs) removes single PDU loss as a point of failure
- UPS
- Two [2] Liebert wet battery systems. Each system is 1 module redundant.
- Capacity
- AP600 system has four [4] 300KVAmodules providing 900KVA capacity with 300KVA reserve power in case 1module fails.
- AP500 system has four [4] 270KVAmodules providing 810KVA capacity with 270KVA reserve power in case 1module fails.
- Critical Load Hours
- 24 Hours Power Back-Up - Utility Power Only
- 20 minute battery back-up at full load
- Extended back-up on partial load or load shedding
- Generators
- Four diesel generators at 1,750 KW each, rated 2,188 KVA
- Output: 480 VAC 3 Phase
- 6000 Gallon and 3000 Gallon underground supply
- Fuel delivered by a dual fuel pumping station.
- Exterior building connections for an alternate source mobile generator.
- Life Safety System
- Building has a dedicated riser which feeds one emergency panel on every 3rd floor. This riser feeds emergency lights and exit lights on all floors. The building does not have an emergency generator. During a power outage, the Data Center space is picked up from the Data Center Generators.
|
| Security |
- 24x7 Guard station
- Elevator code
- Key card plus biometrics
- Escorted at all times
- Closed circuit cameras throughout building
- Fire suppression system
|
| Network |
- Multiple carriers and last mile fiber providers for connectivity
- Redundant core routing for Internet
- Carrier-class routing equipment is used in IPR data centers
- Microwave capabilities available
|